ABSTRACT

Purpose: This study is to address the spacial composition of a standard ward and bedroom size for sake of infection control and efficient medical service. Methods: Spacial composition of a standard ward has been proposed by comparative analysis of 5 big hospitals’ wards. Bedroom sizes have been explored on the ground of Health care facility regulations from Korea, USA, Australia and Canada. Of course, Literature and field survey have been conducted in order to draw out various bedroom sizes. Results: 16 basic and some other additional spaces have been proposed for the composition of hospital standard ward. Area of Single bedroom is 11.6㎡, and that of multi-beded room is 7.4㎡. Bed to bed Clearance is 1.5m, spacing between bedsize and hard wall is 0.9m in 1~2 beded room, 0.75m in 4-beded room. Space clearance between Foot side of bed and curtain is proposed as 0.3m and additional 0.9m is necessary for the circulation. Implications: The result of this study can be applied to the new cons.